FCA 2 REGHE
Product characteristics
- Connection of a fan coil unit with up to 6 fan speeds or connection of fan coil units with up to 3 fan speeds respectively
 - Outputs can be operated manually, construction site mode
 - Modes for heating, cooling or combined heating/cooling operations
 - 2-pipe or 4-pipe operation
 - Individual or hierarchical switching of fan speeds
 - Feedback
 - Disabling function for each channel
 
Operation modes
- Bus operation: operation via touch sensors or room controller
 - Temporary manual control: manual operation locally with keypad, automatic return to bus operation
 - Permanent manual control mode: only manual operation locally on device
 
Technical data
| KNX medium: | TP 256 | 
| KNX supply: | DC 21 … 32 V SELV | 
| Power consumption KNX: | typical 150 mW | 
| Rated voltage: | AC 230/240 V ~, 50/60 Hz | 
| Power loss: | max. 3 W | 
| Ambient temperature: | −5 … +45 °C | 
| Storing temperature: | −25 … +70 °C | 
| Connection, KNX: | terminal | 
| Connection, mains and outputs | |
| Connection mode: | screw terminals | 
| single wire: | 1 x 0.5 … 4 mm² | 
| stranded without ferrule: | 1 x 0.5 … 4 mm² | 
| stranded with ferrule: | 1 x 0.5 … 2.5 mm² | 
| Switch type: | NO contact | 
| Contact type: | floating relay contacts (μ contact) | 
| Switching voltage: | AC 230/240 V ~ | 
| Breaking capacity AC1: | 10 A | 
| Breaking capacity AC3: | 10 A | 
| Switching capacities per output | |
| Ohmic load: | 2300 W | 
| Capacitive load: | 10 A / max. 140 µF | 
| Motors: | 1380 VA | 
| Lamp loads | |
| Incandescent lamps: | 2300 W | 
| HV halogen lamps: | 2300 W | 
| LV halogen lamps with | |
| inductive transformers: | 1200 VA | 
| electronic transformers: | 1500 W | 
| Fluorescent lamps | |
| non-compensated: | 1000 W | 
| parallel compensated: | 1160 W / 140 µF | 
| lead-lag circuit: | 2300 W / 140 µF | 
| Approvals: | VDE | 
	
											
	                        	                        	
          
          