2096 LUX
Intended use
- Measurement and control of lighting indoors or in protected outdoor area
- Clamp mounting in suspended ceilings
- Ceiling installation on fixed ceilings in flush box according to EN 60670-1 with flush mounting set (ref.-no.: PMM-UP-SET-WW)
- Surface-mounted ceiling installation with surface mounting set (ref.-no.: PMM-AP-SET-WW)
Product characteristics
- Asymmetrical measuring surface
- Integrated bus coupling unit
- Integrated brightness sensor
- Brightness sensor function with 3 limiting values
- Brightness limiting values (3 channels) with output functions switching, value transmitter and scene extension
- Light control with max. 3 channels, setpoint shift in operation, separate configuration of dimming-up, control and dimming-down phase
- On-off control possible for switch actuators
- Power supply via bus voltage
Technical data
| KNX medium: | TP 256 | 
| Rated voltage KNX: | DC 21 … 32 V SELV | 
| Current consumption KNX: | max. 10 mA | 
| Connection, KNX: | terminal | 
| Protection class: | III | 
| Ambient temperature: | −25 … +55 °C | 
| Storage/transport temperature: | −25 … +70 °C | 
| Relative humidity: | 10 … 100 % (no condensation) | 
| Protection level: | IP 44 | 
| Ceiling cut-out (Ø x D): | 44 x 35 mm | 
| Dimensions (Ø x H): | 53.5 x 38 mm (with design ring) | 
| Max. thickness of the suspended ceiling: | approx. 25 mm | 
| Installation depth: | min. 35 mm | 
| Distance between concrete ceiling and suspended ceiling: | min. 20 mm | 
| Design ring Ø inside: | 35.6 mm | 
| Design ring Ø outside: | 53.5 mm | 
| Profile height design ring: | 1.8 mm | 
| Profile height lens: | 5.5 mm | 
| Brightness measurement | |
| Measuring range: | 10 … 2,000 lx | 
| Accuracy (> 80 lx): | ± 5 % | 
| Accuracy (≤ 80 lx): | ± 10 lx | 
 
	
											
	                        	                        	 
          

 