23066 REGHE
Intended use
- Switching of electrical loads with floating contacts
 - Switching of electrically-driven blinds, shutters, awnings and similar hangings
 - Switching of electrothermal drives
 - Polling of conventional switching or push-button contacts, window contacts etc. in KNX systems, for reporting of states, meter levels, operation of loads, etc.
 - Polling of external temperature sensors for heating control
 - Logic functions to control building functions
 - Mounting on DIN rail according to EN 60715 in distribution boxes
 
Product characteristics
- Actuator functions: switching, blinds, electrothermal drives
 - Actuator function can be switched in pairs
 - Integrated push-button interface with 6 inputs
 - 2 integrated room temperature controllers
 - 2 inputs for temperature sensors (ref.-no. FF 7.8)
 - Outputs can be operated manually, construction site mode
 - Feedback in manual mode and in bus mode
 - Scene function
 - Disabling of individual outputs manually or via bus
 
Switching function
- 6 switching outputs
 - Operation as NO or NC contacts
 - Logic operation and forcing function
 - Feedback function
 - Central switching function with collective feedback
 - Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
 
Blinds function
- 3 blinds outputs
 - Suitable for 230 V AC motors
 - Blind/shutter position directly controllable
 - Slat position directly controllable
 - Feedback of movement status, blind/shutter position and slat position
 - Forced position through higher-level controller
 - Safety function: rain alarm, frost alarm, 3 independent wind alarms
 - Sun protection function
 
Function of valve drives
- 2 outputs for electrothermal drives
 - Switching operation or PWM operation
 - Actuators with characteristics “normally open” or “normally closed” can be controlled
 - Emergency operation in case of bus voltage failure for summer and winter
 - Protection against jamming valves
 - Forced position
 - Cyclical monitoring of the input signals can be parameterised
 
Heating controller
- 2 internal controllers to control two independent rooms
 - Control for heating or cooling, optionally with additional level
 - On-off, PWM or PI control
 - Predefined heating types (hot water heating, fan coil unit …) or individual parameters possible
 
Inputs
- 6 inputs for push-buttons
 - Input functions: switching, dimming, blinds control, light scene extension unit, brightness or temperature value transmitter
 - 2 inputs for external temperature sensors
 
Logic functions
- Up to 10 logic operations with up to 8 inputs each, e.g. for AND, OR and XOR operations
 - Conversion of data point types, e.g. from 1-bit to 8-bit
 - Comparative operations, e.g. <, >, ≤, ≥
 - Arithmetic functions, e.g. +, –, *, :
 
Technical data
| KNX medium: | TP 256 | 
| Rated voltage KNX: | DC 21 … 32 V SELV | 
| Current consumption KNX: | 4 … 20 mA | 
| Connection, KNX: | terminal | 
| Power loss: | max. 6 W | 
| Ambient temperature: | −5 … +45 °C | 
| Storage/transport temperature: | −25 … +70 °C | 
| Relay outputs | |
| Contact type: | floating relay contacts (μ contact) | 
| Switch type: | NO contact | 
| Switching voltage: | AC 250 V ~ | 
| Min. switching current AC: | 100 mA | 
| Switching current AC1 (cos ϕ > 0.8): | 16 A | 
| Switching current AC3 (cos ϕ < 0.8): | 6 A | 
| Fluorescent lamps: | 16 AX | 
| Switch-on current 200 µs: | max. 800 A | 
| Switch-on current 20 ms: | max. 165 A | 
| Switching voltage DC: | DC 12 … 24 V | 
| Switching current DC 24 V: | 6 A | 
| Connected load, 230 V | |
| Ohmic load: | 3000 W | 
| Blind / Fan motors: | 1380 VA | 
| Lamp loads 230 V | |
| Incandescent lamps: | 3000 W | 
| HV halogen lamps: | 2500 W | 
| HV LED lamps: | max. 400 W | 
| Electronic transformers: | 1500 W | 
| Inductive transformers: | 1200 VA | 
| Fluorescent lamps T5/T8 | |
| non-compensated: | 1000 W | 
| parallel compensated: | 1160 W / 140 µF | 
| lead-lag circuit: | 2300 W / 140 µF | 
| Compact fluorescent lamps | |
| non-compensated: | 1000 W | 
| parallel compensated: | 1160 W / 140 µF | 
| Mercury vapour lamps | |
| non-compensated: | 1000 W | 
| parallel compensated: | 1160 W / 140 µF | 
| Electrothermal valve drives | |
| Cycle time: | min. 15 min | 
| Connection, load | |
| Connection mode: | screw terminals | 
| single wire: | 1 x 0.5 … 4 mm² | 
| stranded without ferrule: | 1 x 0.5 … 4 mm² | 
| stranded with ferrule: | 1 x 0.5 … 2.5 mm² | 
| Inputs | |
| Rated voltage: | DC 3.3 V SELV | 
| Signal duration: | min. 100 ms | 
| NO contacts: | max. 50 | 
| NC contacts: | max. 50 | 
| Cable length: | max. 30 m | 
| Use shielded cables for cable lengths > 3 m. | |
| Connection, inputs: | |
| Connection mode: | screw terminals | 
| single wire: | 1 x 0.08 … 1.5 mm² | 
| stranded without ferrule: | 1 x 0.08 … 1 mm² | 
| stranded with ferrule: | 1 x 0.14 … 0.5 mm² | 
| Mounting width: | 72 mm (4 rail units) | 
	
											
	                        	                        	
          
          